Error and Notification Messages
www.lsi.com/channel/products 255
Action
Allow the verification to complete. Verifications have little overhead in terms
of system performance and keep your units in optimum condition.
To prevent unclean shutdowns, always go through the normal shutdown
procedure. It is also recommended to use an uninterruptible power supply
(UPS) to prevent unclean shutdowns due to sudden power loss.
See Also
“About Verification” on page 155
0009 Drive timeout detected
Event Type
Error
Cause
A drive has failed to respond to a command from a 3ware RAID controller
within the allowed time limit (20 secs.). After sending this error message, the
controller will attempt to recover the drive by sending a reset to that drive and
retrying the failed command.
Possible causes of drive time-outs (also known as ATA-Port time-outs)
include a bad or intermittent disk drive, power cable or interface cable.
Action
If you have checked hardware connections and no cause other than the drive
can be found, replace the drive.
You may also want to use the drive manufacturer’s diagnostic and repair
utilities on the drive.
See Also
For links to drive manufacturer diagnostic utilities and troubleshooting
advice, search the LSI Knowledge Base for keyword 14924 (use the
Advanced Search) at
https://selfservice.lsi.com/service/main.jsp.
“Basic Troubleshooting: Check This First” on page 239